Working Principle
The principle of the SVG is very similar to that of Active harmonic Filter, When the load is generating inductive or capacitive current, it makes load current lagging or leading the voltage. SVG detects the phase angle difference and generates leading or lagging current into the grid, making the phase angle of current almost the same as that of voltage on the transformer side, which means fundamental power factor is unit. YIY-SVG is also capable of correcting load imbalance.

Technical Specifications
Technical Specification | 220V Series | 400V Series | 500V Series | 690V Series |
Rated Compensation Capacity | 5Kvar | 10KVar15KVar/35KVar/50KVar75KVar/100KVar | 90Kvar | 100Kvar/120Kvar |
Nominal Voltage | AC220V(-20%~+15%) | AC400V(-40%~+15%) | AC500V(-20%~+15%) | AC690V(-20%~+15%) |
Rated Frequency | 50/60Hz±5% | |||
Grid Structure | Single phase | 3 phase 3 wire/3 phase 4 wire | ||
Number of paralle | No limitation.A single centralized monitoring module can be equipped with up to 8 power modules. | |||
Machine Efficiency | >97% | |||
Switching Efficiency | 32kHz | 16kHz | 12.8kHz | 12.8kHz |
Function | Reactive /Reactive and Harmonic | Reactive /Reactive and harmonic /Reactive and imbalance (optional) | ||
Reactive Power Compensation Rate | >99% | |||
Harmonic Compensation Capacity | 70%SOC | |||
Harmonic Compensation Times | 2-13 times | |||
Response Time | <10ms | |||
Noise | <50dB | <60dB | <65dB | |
Communication Method | Two-channel RS485 communication interface (support GPRS/WIFI wireless communication) | |||
Monitoring Method | 4.3 inch LCD small-sized screen /7 inch LCD centralized monitoring screen | |||
Protection | Over load protection,hardware/software over current protection,over grid power protection /under grid power protection,grid power voltage imbalance protection,power failure protection,over temperature protection,frequency anomaly protection,short circuit protection,etc | |||
Altitude | ≤2000Meters | ≤2000Meters | ≤2000Meters | ≤2000Meters |
Ambient Temperature | -20~+50°C | -20~+50℃ | -20~+50°C | -20~+50°C |
Relative Humidity | <90%,The average monthly minimum temperature is 25°C without condensation on the surface | |||
Pollution Level | Below level III | |||
nstallation | RackWall-mounted | |||
Wiring Patter | Back entry (Rack type)Top entry (Wall mounted type) | |||
Protection Grade | IP20 | |||
Color | White |
Product naming

Product Appearance